Stuck starter vs unearthed fitting

Makes a bit of a mess! Has actually been on fire by the looks of it

Stuck starter vs unearthed fitting


Makes a bit of a mess! Has actually been on fire by the looks of it

IMG_20171007_215422.jpg IMG_20181115_154331.jpg IMG_20190220_163002-1-1920x1346.jpg IMG_20190301_160034-1.jpg IMG_20190304_213912-1-01.jpeg
File information
Filename:IMG_20190220_163002-1-1920x1346.jpg
Album name:fluorescent / Fail
Filesize:603 KiB
Date added:20 Feb, 2019
Dimensions:1920 x 1346 pixels
Displayed:57 times
URL:http://80.229.24.59:9232/gallery/displayimage.php?pid=10376
Favourites:Add to Favourites

Comment 1 to 11 of 11
Page: 1

Danny   [20 Feb, 2019 at 04:52 PM]
Worst ive seen that.
FrontSideBus   [20 Feb, 2019 at 05:39 PM]
Extra crispy lol. I can smell that from here...
oliver   [20 Feb, 2019 at 05:43 PM]
Looks like it might have been arcing too.
Ash   [20 Feb, 2019 at 06:04 PM]
This have nothing to do with a stuck starter or the Earthing of the fitting. Starters overheat like this when the weld of the bimetal strip inside the glow lamp fails, and the strip detaches from the post. The lamp then will glow continuously without anything that would close the contact and extinguish it, so it heats up until it sets the plastic on fire
AngryHorse   [20 Feb, 2019 at 07:42 PM]
That’s quite bad Surprised
fluorescent   [20 Feb, 2019 at 07:46 PM]
Ash, the unearthed fitting will not help, as from my experience when they get like this they usually track to earth and trip any RCD protection or trip the circuit protection. Not having any earth will almost certainly have allowed this to go on for longer than it might have done otherwise & make a bigger mess!
Danny   [20 Feb, 2019 at 08:15 PM]
Ive only ever seen this from starters continuously trying to strike EOL tubes and overheating plus starters that just stay lit all the time.
fluorescent   [20 Feb, 2019 at 09:34 PM]
The tube fitted was an EOL Sylvania, it had probably been flashing away for a long time... I've fixed this now, removed what was left of the old starter & holder, used some mildly abrasive cleaner to get the worst of the carbon deposits off and fitted a used BJB starter holder from an 8ft fitting I scrapped recently. Good as new now (ish!)
Danny   [20 Feb, 2019 at 09:44 PM]
Good work!
fluorescent   [20 Feb, 2019 at 10:22 PM]
Only problem now... I have no lamp holder springs for this fitting as I robbed them for use on another one, doh! Never mind, should have something in the parts bin that'll do the job hopefully
Ash   [21 Feb, 2019 at 10:20 PM]
In my Fitzy's the starter holder is something unique that mounts to a square hole in the back of the lightpack body. I don't know of any other starter socket with the same mounting. Are the newer lightpacks different ?