I had just the same a while back here in Israel : Compressor at a factory not starting because line voltage is about 213V (measured at the service drop disconnect). (Some asinine computerized "smart" thing yet it can't even throw out a meaningful error). Called IEC. They checked that all other customers powered from the same transformer would be ok with a higher tap, and changed the tap. Now its good 230..240, but in off-peak times (when this factory and others around are closed) the line voltage is somewhere in the 250V ballpark. A bit high but i can't think of anything that would be actually damaged. (Nobody uses incandescent lamps there, any heaters etc are on a thermostat anyway so it would only change their cycling times)